  1. Triggers are not supported as part of a move command.

  2. When appliance restarts, the Ubuntu OS routing table is added with a duplicate default gateway pointing to the IP address assigned by the PLC. This is causing loss of internet access until the duplicate default gateway in the Ubuntu routing table is manually cleared. This is related to Ubuntu OS. Workaround: after Profinet is running, issue sudo ip route del default to restore internet access from the RTR controller.

  3. Occasionally the PLC triggers a Profinet watchdog error. This is due to the Ubuntu Desktop OS is not optimized for real-time communication. OS thread priority should be fine tuned. Workaround: increase the number of retries in the Profinet device IO settings in TIA Portal, while keeping the same 2mS update time.

  4. The Profinet driver is tested on RTR controllers(V1 and runtime) only.

...

  1. DSM boxes, objects, and frames are tracked in the Profinet look up ID table. When items are created or removed, their Profinet IO mappings are handled as such, the handler retrieves the new id of the entity, and publishes it with Profinet. However, this does not cover cases where an external command source elicits a change in the DSM that’s unknown to a PLC.

Typical communication latencies

...

The charts below measure the time delay between a move command sent by a PLC and the ACK signal received by a PLC, with PNIO update time = 2mS.

...